<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Archiving and Interchange DTD with MathML3 v1.3 20210610//EN" "https://jats.nlm.nih.gov/archiving/1.3/JATS-archivearticle1-3-mathml3.dtd">
<article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" xmlns:ali="http://www.niso.org/schemas/ali/1.0/" dtd-version="1.3" article-type="research-article" xml:lang="en">
  <front>
    <journal-meta>
      <journal-id journal-id-type="publisher-id">journal-of-applied-sciences</journal-id>
      <journal-title-group>
        <journal-title>Journal of Applied Sciences</journal-title>
      </journal-title-group>
      <issn publication-format="electronic">2998-9159</issn>
      <publisher>
        <publisher-name>Directive Publications</publisher-name>
      </publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.52338/joas.2025.5099</article-id>
      <article-categories>
        <subj-group subj-group-type="heading">
          <subject>Research</subject>
        </subj-group>
      </article-categories>
      <title-group>
        <article-title>Design and Engineering Testing of a Neutral Line Current Eliminator</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author" corresp="yes">
          <name>
            <surname>Zhao</surname>
            <given-names>Xuxin</given-names>
          </name>
          <xref ref-type="aff" rid="aff1">1</xref>
        </contrib>
        <contrib contrib-type="author">
          <name>
            <surname>Luo</surname>
            <given-names>Fuman</given-names>
          </name>
          <xref ref-type="aff" rid="aff2">2</xref>
        </contrib>
        <aff id="aff1"><label>1</label>College of Chemistry and Environmental Engineering, Shenzhen University, Shenzhen 518060, Guangdong, China</aff>
        <aff id="aff2"><label>2</label>Shenzhen Xinhengji Electric Appliance Co., Ltd, Shenzhen 518000, Guangdong, China</aff>
      </contrib-group>
      <pub-date publication-format="electronic" date-type="pub" iso-8601-date="2025-10-06">
        <day>06</day>
        <month>10</month>
        <year>2025</year>
      </pub-date>
      <volume>13</volume>
      <issue>1</issue>
      <history>
        <date date-type="received" iso-8601-date="2025-09-06">
          <day>06</day>
          <month>09</month>
          <year>2025</year>
        </date>
      </history>
      <permissions>
        <copyright-statement>© 2025 The Author(s). Published by Directive Publications.</copyright-statement>
        <copyright-year>2025</copyright-year>
        <copyright-holder>The Author(s)</copyright-holder>
        <license license-type="open-access" xlink:href="https://creativecommons.org/licenses/by/4.0/">
          <ali:license_ref>https://creativecommons.org/licenses/by/4.0/</ali:license_ref>
          <license-p>This is an open access article distributed under the terms of the CC BY 4.0 licence (https://creativecommons.org/licenses/by/4.0/).</license-p>
        </license>
      </permissions>
      <self-uri content-type="html" xlink:href="https://directivepublications.org/journal-of-applied-sciences/design-and-engineering-testing-of-a-neutral-line-current-eliminator"/>
      <self-uri content-type="pdf" xlink:href="https://directivepublications.org/pdf/180/design-and-engineering-testing-of-a-neutral-line-current-eliminator.pdf"/>
      <abstract>
        <p>This paper proposes a device to reduce neutral line current based on the principle of magnetic flux compensation. The device achieves phase shifting through a specially designed magnetic circuit transformer with adjustable coils, generating magnetic fluxes of equal magnitude but opposite direction to counteract the harmonic-induced fluxes, thereby suppressing neutral line current. The circuit design of the neutral line current eliminator is introduced. Measurements conducted on actual engineering loads show that the harmonic current on the neutral line is reduced by more than 90%.</p>
      </abstract>
      <kwd-group kwd-group-type="author">
        <kwd>Magnetic Flux Compensation</kwd>
        <kwd>Neutral Line Current</kwd>
        <kwd>Neutral Line Current Eliminator</kwd>
        <kwd>Phase Shifting Method</kwd>
      </kwd-group>
    </article-meta>
  </front>
  <body>
    <sec id="introduction">
      <label>1</label>
      <title>Introduction</title>
      <p>In modern power systems, harmonic pollution caused by the widespread use of nonlinear loads has become a significant factor in the degradation of power quality. Nonlinear loads generate harmonic currents of various frequencies, especially zero-sequence harmonics that accumulate on the neutral line, leading to overheating and, in severe cases, damage or even fire, posing risks to the safe and stable operation of power systems<sup>[<xref ref-type="bibr" rid="ref-1">1</xref>]</sup>. Therefore, addressing the issue of excessive neutral line current is of great importance.</p>
      <p>This paper proposes a device to reduce neutral line current based on the principle of magnetic flux compensation<sup>[<xref ref-type="bibr" rid="ref-2">2</xref>]</sup>. The device achieves phase shifting through a specially designed magnetic circuit transformer with adjustable coils, generating magnetic fluxes of equal magnitude but opposite direction to counteract the harmonic-induced fluxes, thereby suppressing neutral line current. The circuit design of the neutral line current eliminator is introduced. Measurements conducted on actual engineering loads show that the harmonic current on the neutral line is reduced by more than 90%.</p>
    </sec>
    <sec id="design-of-the-neutral-line-current-eliminator">
      <label>2</label>
      <title>Design of the Neutral Line Current Eliminator</title>
      <p>The neutral line current eliminator(NCE), designed with an improved zigzag phase-shifting zero-sequence magnetic flux compensation circuit, is shown in <bold>Figure <xref ref-type="fig" rid="figure-1">1</xref></bold>. It mainly consists of a magnetic circuit three-phase transformer, a sampling unit, a controller, and an actuation unit. The controller is electrically connected to the sampling unit and the actuation unit, the actuation unit is electrically connected to the magnetic circuit three-phase transformer, and the magnetic circuit three-phase transformer is connected to the load<sup>[<xref ref-type="bibr" rid="ref-3">3</xref>-<xref ref-type="bibr" rid="ref-6">6</xref>]</sup>.</p>
      <fig id="figure-1">
        <label>Figure 1</label>
        <caption>
          <p>Structure of the NCE.</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-1.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <p><bold>Sampling Unit</bold>: Collects the voltages of the A, B, and C phases of the load, the currents of the A, B, C, and N lines, and the voltages and currents of a2 and c1 in the open-delta connection.</p>
      <p><bold>Controller</bold>: Calculates the collected voltages of the A, B, and C phases, the currents of the A, B, C, and N lines, and the voltages and currents of a2 and c1 in the open-delta connection; calculates the magnetic flux generated by the zero-sequence current of the load and its direction in the core; calculates the required voltage and phase-shifting angle to generate the reverse magnetic flux; outputs control commands to the actuation unit.</p>
      <p><bold>Actuation Unit</bold>: Controls the phase-shifting angle and capacity by adjusting the number of turns of three sets of adjustable secondary coils, generating a reverse magnetic flux to counteract the original zero-sequence magnetic flux. The actuation unit adjusts the number of turns of the coils according to the instructions.</p>
      <p><bold>Magnetic Circuit Three-Phase Transformer</bold>: The capacity of the three sets of adjustable coils is designed based on the magnitude of the neutral line current. Each set is connected in a head-to-tail delta configuration, controlling the magnetic flux direction by adjusting the phase-shifting angle and the capacity by adjusting the voltage.</p>
    </sec>
    <sec id="wiring-diagram-of-the-neutral-line-current-elimi">
      <label>3</label>
      <title>Wiring Diagram of the Neutral Line Current Eliminator</title>
      <p>The connection of the neutral line current eliminator to the load equipment is shown in <bold>Figure <xref ref-type="fig" rid="figure-2">2</xref></bold>. The current measurement points in the test are A1 to A4. A1, A2, and A3 record the line currents on the power supply side, while A4 records the neutral line current on the power supply side.</p>
      <fig id="figure-2">
        <label>Figure 2</label>
        <caption>
          <p>Wiring Diagram of the NCE.</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-2.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <p>4. Test Results and Discussion</p>
      <p>Based on preliminary tests of the LED load characteristics at a commercial plaza in Shenzhen, the neutral line current eliminator designed in this paper was tested in an engineering trial. The test results are shown in <bold>Figures <xref ref-type="fig" rid="figure-3">3</xref> </bold>to<bold> 6</bold>.</p>
      <fig id="figure-3">
        <label>Figure 3</label>
        <caption>
          <p>Neutral line current before the operation of the NCE.</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-3.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <fig id="figure-4">
        <label>Figure 4</label>
        <caption>
          <p>Neutral line current after the operation of the NCE</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-4.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <p>From <bold>Figures <xref ref-type="fig" rid="figure-3">3</xref> </bold>and<bold> 4,</bold> it can be observed that the neutral line current decreased from 191.3 A to 11.9 A, achieving a neutral line current reduction rate of 93.8%. This indicates that the neutral line current eliminator has a significant effect on reducing neutral line current in engineering trials.</p>
      <fig id="figure-5">
        <label>Figure 5</label>
        <caption>
          <p>Harmonic current before the operation of the NCE.</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-5.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <fig id="figure-6">
        <label>Figure 6</label>
        <caption>
          <p>Harmonic current after the operation of the NCE.</p>
        </caption>
        <graphic xlink:href="https://directivepublications.org/storage/ftv2/180-ff88eecbaf0a6f5ba768/fig-figure-6.png" mimetype="image" mime-subtype="png"/>
      </fig>
      <p>From <bold>Figures <xref ref-type="fig" rid="figure-5">5</xref> </bold>and<bold> 6</bold>, it can be seen that the 3rd harmonic current content in the three phases decreased from 42.2%, 40.2%, and 31.1% to 11.1%, 5.5%, and 8.8%, respectively. This demonstrates that the neutral line current eliminator has a high removal rate for the 3rd harmonic.</p>
    </sec>
  </body>
  <back>
    <ref-list>
      <title>References</title>
      <ref id="ref-1">
        <label>1</label>
        <mixed-citation>Kang Peng, Guo Wei. Overview of Power Quality Issues and Key Mitigation Technologies in Regional Power Grids. Electrical Measurement &amp; Instrumentation. 2020; 57(24):1-4.</mixed-citation>
      </ref>
      <ref id="ref-2">
        <label>2</label>
        <mixed-citation>Fuman Luo. Electrical Fire Hazards Caused by Excessive Zero-Line Current from LED Lighting. Light &amp; Lighting. 2019; 43(4): 51-54.</mixed-citation>
      </ref>
      <ref id="ref-3">
        <label>3</label>
        <mixed-citation>Mohit Bajaj, Amit Kumar Singh. Optimal design of passive power filter for enhancing the harmonic-constrained hosting capacity of renewable DG systems. Computers and Electrical Engineering. 97 (2022) 107646.</mixed-citation>
      </ref>
      <ref id="ref-4">
        <label>4</label>
        <mixed-citation>H. M. Jeewantha De Silva, Mohammad Shafieipour. An improved passivity enforcement algorithm for transmission line models using passive filters. Electric Power Systems Research. 196 (2021) 107255.</mixed-citation>